Question 1

A computer room with raised floor and hot/cold aisles is designed. What is the minimum required distance between the air-conditioner outlet and the first rack?

Options:

A.

None

B.

60 cm (2 ft)

C.

120 cm (4 ft)

D.

180 cm (6 ft)

Question 2

What indicates the breaking capacity of a fuse or breaker?

Options:

A.

Mechanical strength of the casing of a fuse or breaker.

B.

The maximum voltage, in case of an electrical surge, that the fuse or breaker can handle without being destroyed or causing an electric damaging arc.

C.

The current at which the device will trip.

D.

The current that a fuse or breaker is able to interrupt without being destroyed or causing an electric damaging arc.

Question 3

A new facility requires electrical distribution of 100A to be installed in the computer room, 1 m (3 ft) above sensitive IT equipment. What type of system minimizes EMF impact?

Options:

A.

Install single-phase power cabling

B.

Install three-phase power cabling based on three individual core wires

C.

Install bus bar trunking

D.

Install three-phase power cabling based on a combined cable (e.g., XLPE)

Question 4

A battery bank has 800 Ah total capacity. How much charging current should the rectifier be able to supply?

Options:

A.

40 A

B.

60 A

C.

80 A

D.

160 A

Question 5

What is the minimum requirement for power feeds to a Rated-4 data center (ANSI/TIA-942)?

Options:

A.

Two feeds from two different substations, one power company not acceptable

B.

Two feeds from two different substations, one power company acceptable

C.

Two feeds from one substation

D.

One feed split into two distribution boards

Question 6

A data center scores Rated-3 in mechanical, Rated-4 in electrical, and Rated-2 in telecommunications. What is the overall rating?

Options:

A.

Rated-2

B.

Rated-4

C.

Rated-4 since electrical is most important

D.

Depends on architectural rating

Question 7

In which stage of the data center life cycle does commissioning take place?

Options:

A.

Retire

B.

Operate/optimize

C.

Implement

D.

Design

Question 8

A computer room with a raised floor has been designed with racks in a hot/cold aisle setup.

What should you recommend for the placement of down-flow air conditioners?

Options:

A.

Air conditioners perpendicular to (at the end of the row of) the Cold-Aisle

B.

Air conditioners perpendicular to (at the end of the row of) the Hot-Aisle

C.

Air conditioners should always be placed at both sides of each row of racks

D.

Air conditioner placement has no influence on cooling effectiveness and efficiency. Hence, they can be placed at any convenient location.

Question 9

A data center is in an area where utility power is highly available—only a few outages per year, typically <1 hour per event and <50 hours/year not available. What type of generators should be installed?

Options:

A.

Continuous generators in at least N+1

B.

A combination of standby, prime, and continuous sized to 500% of the load

C.

Standby generators; no N+1 needed as the risk of a failure to start is negligible

D.

Standby generators, ideally in an N+1 configuration

Question 10

You want to make cooling more effective by setting cold aisle temperature to 4 °C (39 °F). Is this acceptable?

Options:

A.

Yes, but only if cooling systems can maintain this continuously

B.

Yes, as long as dewpoint doesn’t go below -9 °C (16 °F)

C.

No, 4 °C (39 °F) is below the allowable ASHRAE range

D.

No, intake air must be exactly 20 °C (68 °F)

Question 11

You need to install a highly sensitive fire detection system. The data center has a high airflow rate. Which system should you recommend?

Options:

A.

Dry pipe sprinkler system

B.

Ionization smoke detector

C.

Photoelectric smoke detector

D.

VIEW (Very Early Warning) smoke detector

Question 12

What is the advantage of OM5 multimode fiber cabling?

Options:

A.

Supports SWDM, requiring fewer fibers

B.

No advantage—same as OM4

C.

Designed for cheaper LED transmitters

D.

100 Gbit/s link for 500 m reach

Question 13

You want to manage temperature and humidity only at the facility level in your data center. All servers use front-to-rear airflow. Which location for measurement should you recommend?

Options:

A.

At the back/rear of the server at 50 mm (2 in)

B.

At 1.5 m (5 ft) above the floor, 0.4 m (15 in) in front of the rack

C.

At the front/intake of the server at 50 mm (2 in)

D.

At 1.5 m (5 ft) above the floor, 0.4 m (15 in) at the back of the rack

Question 14

Do you need to consider bullet (ballistic) protection when designing a data center?

Options:

A.

No; bullet protection is not a requirement of ANSI/TIA-942

B.

No, there is no reason for implementing bullet protection as you cannot predict the type of weapons that might be used

C.

Yes, but only when the data center is built in an area with a high criminality rate or with a risk of terrorist attacks

D.

Yes, bullet protection is a requirement of ANSI/TIA-942 for Rated-3/4 data centers

Question 15

You have three UPS systems connected in parallel. The UPS systems have an imbalance in the load sharing of approximately 20%.

What should you recommend?

Options:

A.

Review the cable lengths of each UPS to the common busbar

B.

Nothing, there is no reason for any concern

C.

Review the common mode noise levels within the computer room

D.

Review the harmonics levels within the computer room

Question 16

Given: A = attenuation in dB, R = real measured value, M = maximum acceptable value. Which formula should be used to calculate the required attenuation factor of EMF shielding material?

Options:

A.

A = 10 log (R/M)

B.

A = 20 log (M/R)

C.

A = 10 log (M/R)

D.

A = 20 log (R/M)

Question 17

When installing a raised floor, can we use a spirit level bar to level the floor?

Options:

A.

Yes, spirit level bars can be used as long as their length is longer than 60 cm/2 ft (the size of a typical raised floor tile).

B.

No, because using a spirit level bar, a measurement error will be transferred from pedestal to pedestal.

C.

Yes, but spirit level bars can only be used in the vertical plane.

D.

Yes, using a spirit level bar for raised floors higher than 40 cm is preferred.

Question 18

What is the advantage of using Multi-fiber Push-On (MPO) connectors?

Options:

A.

No advantage, cannot be used with OM4 fiber

B.

Allows a single connector with multiple fibers running parallel, enabling easy upgrade to 40–100 Gbit/s

C.

Made of high-quality materials, reusable without risk

D.

Very flexible, can be used for both copper and optical fiber

Question 19

The UPS of a data center with ANSI/TIA-942 Rating-4 is installed with the rectifier connected to power feed A and the bypass/reserve input connected to power feed B. To which feed will the UPS output be synchronized?

Options:

A.

Feed A

B.

Feed B

C.

The UPS will not synchronize to any feed but use an internal clock

D.

Depends on UPS settings, as it can be set to either feed

Question 20

What should you consider when using raised floor tiles with air deflectors or louvers?

Options:

A.

Tiles with air deflectors or louvers can be very heavy.

B.

Tiles with air deflectors or louvers will reduce the cooling capacity of the tile.

C.

Tiles with air deflectors or louvers do not allow for a flexible cooling solution.

D.

Tiles with air deflectors or louvers can only be used to cool storage equipment.

Question 21

When shielding material reaches its saturation point, what will be the impact?

Options:

A.

The shielding material will reach its optimal shielding performance state.

B.

The shielding material will no longer be able to attenuate (reduce) additional EMF.

C.

The shielding material will increase its permeability factor.

D.

The shielding material will reach its maximum electrically charged state.

Question 22

A data center is located in an area where the demand for power is higher than the utility power company is able to deliver. This results in frequent power outages and, therefore, power shedding (scheduled/controlled power shutdown for areas) is frequently applied. The mains power is more than 650 hours/year not available.

What type of generators should be installed?

Options:

A.

Standby generators should be installed in at least an N+1 configuration

B.

Continuous generators should be installed, at least in an N+1 configuration

C.

A combination of standby-, prime-, and continuous-generators, as the duration of the power outage is unpredictable. The total available capacity of the generators should be at least 500% of the data center load

D.

Continuous generators should be installed; no N+1 configuration is needed as the generators will run all the time

Question 23

What is a disadvantage of hypoxic-based fire suppression?

Options:

A.

Only usable in non-occupied areas

B.

Only usable in rooms with sufficient air changes

C.

Gas containers must be close to hazard

D.

Only usable with positive pressure rooms

Question 24

Smoke sensors need to be tested to ensure that they pick up a potential fire in the data center.

What should you recommend?

Options:

A.

Test the sensors by injecting smoke or simulated smoke directly into the sensor

B.

Press the self-test button on each sensor in the data center

C.

Inject smoke at the floor level

D.

Test the sensors according to the vendor specification

Question 25

What is the calculation for the desired attenuation factor for shielding material?

Options:

A.

A = 20 log (M / R)

Where

A is Attenuation

M is the maximum acceptable value

R is the real value measured

B.

A = M / R

Where

C.

A is Attenuation

M is the maximum acceptable value

R is the real value measured

D.

A = 20 log (R / M)

Where

A is Attenuation

R is the real value measured

M is the maximum acceptable value

E.

You do not have to calculate the attenuation factor for shielding material as it always has the same attenuation

Question 26

Can you install a raised floor tight to the perimeter of the room?

Options:

A.

Yes, but only if the data center is located in Zone 0 with no or little seismic activity

B.

Yes, a raised floor needs to be installed tight to the perimeter to prevent air leakage

C.

No, to avoid damage to the raised floor due to building and hygrothermal movement

D.

No, but this applies only to raised floors with a height of over 90 cm (3 ft)

Question 27

What is a significant difference between a halocarbon gas-based fire suppression system and an inert gas-based fire suppression system?

Options:

A.

Inert gas has smaller-sized gas containers than halocarbon gas.

B.

Inert gas harms the environment and halocarbon gas does not.

C.

Halocarbon gas works on the basis of heat removal and inert gas works on the basis of oxygen reduction.

D.

Halocarbon gas works on the basis of oxygen reduction and inert gas works on the basis of heat removal.

Question 28

What is a potential disadvantage of using water mist as a fire extinguishing system?

Options:

A.

It only uses 10% of the water normally used in a water-based fire suppression, which might not be enough to suppress the fire

B.

It will rapidly increase the humidity level in the data center, which can cause a potential risk for the operation of the equipment

C.

It extracts oxygen from the air creating a potential risk for humans inside the computer room

D.

It has droplets that are too small (100-120 microns) so it can only be used for small fires

Question 29

Management requests a 15-minute battery bank at full UPS load. UPS specs:

    30 kVA, PF 0.8

    Battery 384 V (192 cells), end discharge 308 V

    Inverter PF 0.8, 400 V output

What information is missing to perform the calculation?

Options:

A.

UPS efficiency

B.

Inverter efficiency / output PF

C.

Load imbalance

D.

Available battery charging current

Question 30

What is the risk of high levels of hydrogen sulfide (H₂S) in the computer room?

Options:

A.

There is no risk

B.

H₂S impacts the static properties of the floor

C.

H₂S can cause corrosion which impacts reliability of equipment

D.

H₂S impacts gas-based fire suppression system operation

Question 31

What is the preferred way to measure dust levels in the computer room?

Options:

A.

With an air particle hand-held analyzer

B.

With test coupons

C.

By taking dust samples under the raised floor

D.

By opening up equipment for inspection

Question 32

A computer room is fitted with a hypoxic-based fire suppression system. On what principle does it work?

Options:

A.

It removes the heat from the fire

B.

It lowers the oxygen levels in the room

C.

It removes the fuel from the fire

D.

It uses water as an extinguisher

Question 33

The 'maximum exposed area' of the fire-rated glass is defined by the supplier as 3 sqm/32 sqft. The window area is 4 sqm/43 sqft.

What would be the best option?

Options:

A.

Do not use fire-rated glass due to the size limit and replace it with normal glass.

B.

Split the window in two equal parts using an aluminum frame.

C.

Split the window into parts smaller than specified as the maximum exposed area and ensure fire-rated frames are used.

D.

Split the window in two equal parts fitted together with transparent silicon glue.

Question 34

What is the main reason to install Earth Leakage protection?

Options:

A.

Protection of ICT equipment against high-frequency noise currents

B.

Protection of human lives

C.

Improvement of the data center grounding/earthing system

D.

Protection against lightning strikes

Question 35

Do all residual current devices (RCDs) use the same operating principle?

Options:

A.

Yes, they all detect current differences on live and neutral wire

B.

Yes, they all measure voltage on the earth conductor

C.

No, ELCB measures earth voltage, whereas RCD detects current differences

D.

No, depending on regulations some use thermal-magnetic operation

Question 36

Three data centers are benchmarked on facilities energy efficiency.

Data center A has achieved a PUE of 2.45.

Data center B has achieved a PUE of 1.20.

Data center C has achieved a PUE of 1.90.

Which of the data centers is operating at the highest facility efficiency?

Options:

A.

PUE does not indicate efficiency

B.

Data center A

C.

Data center B

D.

Data center C

Page: 1 / 12
Total 120 questions